2. Declaration of Conformity
The device was tested according to the applicable standards.
Conformity was proofed. The declaration of conformity is
available at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of
the device. In case of questions that cannot be answered with
these instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to
the Federal Republic of Germany. If the device is used in other
countries it applies to the equipment installer or the user to
meet the national directions.
Safety Instructions
Keep the applicable directions for industrial safety and preventi-
on of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installati-
on or maintenance of the devices.
Only qualified personnel shall do mounting and installation
work with the devices, see section “qualified personnel”.
The information of these instructions have to be read and un-
derstood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are
persons who are well versed in the use and installation of such
devices and whose professional qualification meets the require-
ments of their work.
This includes for example:
Qualification to connect the device according to the VDE
specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate
it by respecting the internal directions.
Knowledge of safety rules.
Knowledge about application and use of the device within the
equipment system etc.
1. Description
The Modbus module with 8 individually configurable
resistance or voltage inputs is designed for local switching
operations. It is suitable to record resistance or voltage values of
for example passive and active temperature sensors electrical
ventilation or mixing valves, valve positions etc. The inputs are
universally configurable and can be scanned via a Modbus-Master.
Setting of the slave address, bit rate and parity is done with the
two address switches (x1 / x10) on the front. Possible settings
are addresses 00 to 99 and baud rates 1200, 2400, 4800, 9600,
19200, 38400, 57600 und 115200 Bd.
The device does not participate in bus communication if the
address is 00 (reserved for broadcast commands).
7170/899289
Analog Input Module
MR-AI8
11083213
5. Connection Diagram
4. Wiring Diagram3. Technical Data
Modbus Interface
Protocoll Modbus RTU
Transmission rate 1200 ... 115200 Bd
(factory setting 19200 Bd Even)
Cabling RS485 two wire bus with voltage
equalizing cable in bus / line
topology
Supply
Operating voltage range 20 ... 28 V AC/DC (SELV)
Current consumption 65 mA (AC) / 25 mA (DC)
Relative duty cycle 100 %
Input
Resistance range 40 W to 4 MW
Voltage input 0 ... 10 V DC
Resolution 1 mV
Error
Voltage input about ±10 mV
Resistance input < 12 kW = 0,1 % / > 12 kW = 1 %
Housing
Dimensions WxHxD 2.0 x 2.8 x 2.6 in. (50 x 70 x 65 mm)
Weight 104 g
Mounting position any
Mounting standard rail TH35 per IEC 60715
Mounting in series the maximum quantity of modules
without space connected in line is limited to 15 or to
a maximum power consumption of
2 Amps (AC or DC) per connection to
the power supply.
For any similar block of additional
modules a separate connection to the
power supply is mandatory.
Material
Housing Polyamide 6.6 V0
Terminal blocks Polyamide 6.6 V0
Cover plate Polycarbonate
Type of protection
(IEC 60529)
Housing IP40
Terminal blocks IP20
Terminal blocks
Supply and bus
4 pole terminal block max. AWG 16 (1,5 mm²) solid wire
max. AWG 18 (1,0 mm²) stranded wire
Wire diameter min. 0.3 mm up to max. 1.4 mm
(terminal block and jumper plug are
included to each packing unit)
Module connection
Input/Output max. AWG 12 (4.0 mm²) solid wire
max. AWG 14 (2.5 mm²) stranded wire
Wire diameter min. 0.3 mm up to max 2.7 mm
Temperature range
Operation -5 °C ... +55 °C
Storage -20 °C ... +70 °C
Protective circuitry polarity reversal protection of
operating voltage
polarity reversal protection of supply
and bus
Display
Operating and bus activity green LED
Error indication red LED
METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH
Mounting instruction see www.metz-connect.com
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Analog Input Module

2. Declaration of Conformity The device was tested according to the applicable standards. Conformity was proofed. The declaration of conformity is ava

Page 2 - 10.1 I/O Commands

7. Bit rate and Parity settingThe bit rate and parity can be set in the programming mode when ajumper is plugged behind the front cover of the module.

Page 3 - Modbus-Funktionen

Continuation Software DescriptionConfigurations Registers are shown above in a way to display the meaning of the individual bit. For the application i

Page 4 - 10.3 General Commands

Continuation Software DescriptionExample for a frame:Slave address 0x12 Setting of rotary switch (18)Function 0x06 Write Single RegisterRegister a