6.3.3 Binary Input Configuring
You can define any channel 1–6 as type INPUT: Binary as shown in Figure 26 which uses
Channel 1 as an example. The channel BACnet type will be Binary Input. On this screen, you
can adjust the following parameters.
Channel Name You can name the channel using no more than 63 characters. This
will be the object name for this channel (followed by the channel
number). For example, “Binary Input-1”.
BACnet Unit Group The Others default can be set to any option in the list.
BACnet Unit Value The NO_UNITS default can be set to any option in the list. The
available options depend on the BACnet Unit Group you specify.
BACnet Description You can enter any string using no more than 63 characters.
Figure 26 Binary Input Configuration