20-point BACnet/IP Sedona Field Controller INSTALLATION GUIDE INTRODUCTION The BAScontrol20 (BASC20) is a 20-point field controller with a direct
TD100700-0IA 10 Analog Outputs AO1–AO4 Voltage in the range of 0–10 VDC (with up to 4 mA of current) can be outputted. No configuration is necessa
TD100700-0IA 11 Binary Inputs BI1–BI4 To sense the action of a push-button or relay, the contacts must have no applied energy, and be rated for low
TD100700-0IA 12 Figure 12 — Steps for Changing the IP Address of the PC Used for Setup Webpage Configuration The BASC20 contains a web server — bro
TD100700-0IA 13 NEED MORE HELP INSTALLING THIS PRODUCT? Additional information can be found in the technical documentation available on our web sit
TD100700-0IA 14 [This page is intentionally blank.]
TD100700-0IA 15 [This page is intentionally blank.]
TD100700-0IA 16 [This page is intentionally blank.]
TD100700-0IA 2 SPECIFICATIONS Universal Inputs (Points UI1 – UI8) (web page configurable) Analog inputs: 0–10 VDC or 0–20 mA (with external resi
TD100700-0IA 3 Figure 1 — RJ-45 Jack Electrical (± 10%) (Intended for use with Class 2 circuits.) Input (DC or AC) DC AC Voltage (V, ±10%):
TD100700-0IA 4 INSTALLATION The BASC20 is intended to be panel-mounted in an industrial enclosure or wiring closet with screws (not provided). See
TD100700-0IA 5 Powering The unit requires a source of 24 VDC or VAC via a two-pin removable keyed connector. NOTE: This device is intended for use
TD100700-0IA 6 Field Connections When attaching devices, observe proper cabling using Figure 3 as a guide. Figure 3 — Sample Wiring Diagram Attach
TD100700-0IA 7 Universal Input — Configured for Analog Input A Universal Input can measure voltage in the range of 0–10 VDC or current in the range
TD100700-0IA 8 Universal Input — Configured for Binary Input To sense the action of a push-button or relay, the contacts must have no applied energ
TD100700-0IA 9 Universal Input — Configured for Pulse Input Assuming a 50% duty cycle, a pulse rate up to 40 Hz can be measured on channels UI1–UI4
Commentaires sur ces manuels