BASR Versatile Building Automation Appliance INSTALLATION GUIDE INTRODUCTION The BAS Remote series provide the system integrator a flexible
TD040300-0II 10 POWERING The unit (except for the BASR-8M/P) requires 24 VDC or VAC from a source via a three-pin removable keyed connector. The
TD040300-0II 11 Connect the HOT side of the secondary to the HI input on the BASR and the LO side to COM on the BASR. All other half-wave devices
TD040300-0II 12 FIELD CONNECTIONS When attaching devices, observe proper cabling using Figure 9 as a guide. Figure 9 — Sample Wiring Diagram Wire
TD040300-0II 13 Thermistors The BAS Remote has built-in calibration curves for 10 kΩ Type II or Type III thermistors. These devices are no
TD040300-0II 14 common mechanical contacts, polarity is not an issue. The open-circuit voltage is 24 VDC and the short-circuit current is 2 mA.
TD040300-0II 15 Pulse Inputs A variation on contact closure inputs is pulse inputs. In this situation speed is critical so the input filtering th
TD040300-0II 16 excursions will be ignored. It is still possible to detect the input signal by only sensing the positive excursions. When interf
TD040300-0II 17 as that loop supply has a common connection with the BAS Remote. The less positive connection is made to point A on the input. F
TD040300-0II 18 Analog Output Either voltage in the range of 0–10 VDC or current in the range of 0–20 mA can be outputted by assigning analog outp
TD040300-0II 19 NEED MORE HELP INSTALLING THIS PRODUCT? Additional information can be found in the technical documentation available on our web si
TD040300-0II 2 The BAS Remote Master provides the ultimate in flexibility. It can be used for expansion I/O at remote locations where an Et
TD040300-0II 20 [This page is intentionally left bank.]
TD040300-0II 3 SPECIFICATIONS Electrical (± 10%) BASR-8M/P BASR-8M BASR-8X DC AC DC AC DC AC Input voltage: 48 V N/A 24 V 24 V 24 V
TD040300-0II 4 Environmental Operating temperature: 0°C to +60°C Storage temperature: –40°C to +85°C Humidity: 10% to 95%, non-condensing U
TD040300-0II 5 PRODUCT IMAGES (WITH PANEL-MOUNTING TABS REMOVED) Figure 2 — BAS Remote Master Image Figure 3 — BAS Remote Expansion Image
TD040300-0II 6 PRODUCT IMAGE (WITH PANEL-MOUNTING TABS REMOVED) Figure 4 — BAS Remote PoE Image MECHANICAL (WITH PANEL-MOUNTING TABS DISPLAYE
TD040300-0II 7 INSTALLATION The BASR is intended to be mounted in an industrial enclosure or wiring closet on 35-mm DIN-rail or panel-
TD040300-0II 8 Modbus Serial Bus Connections The Modbus serial expansion port (MB) on the BAS Remote Master module is non-isolated EIA-485 compati
TD040300-0II 9 CABLING CONSIDERATIONS When attaching cables to the BASR, Table 1 should be considered. Function Signalling & Data Rate Minimum