Contemporary-control-systems BAScontrol20 User Manual Manuel d'utilisateur Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 53
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
TD100700-0MB
38
5.2.6 Analog Outputs (Channels AO1AO4)
Voltage in the range of 010 VDC (with up to 4 mA of current) can be outputted by
assigning analog outputs. Configure an output using a web browser. For DC
voltage, the output voltage is applied to point A with respect to C (common).
Any channel AO1AO4 can be used to provide an analog voltage output. The
BACnet type will be Analog Output. To configure an analog output:
On the Main Page (Figure 13), click a title link from among AO1AO4.
Under BAS Channel Configuration (lower) section of the new screen that
appears (Figure 24), the Channel Type will be Analog Output (read-only).
In the BACnet Object Configuration (lower) section of the screen, all items
are as described in Section 5.2 above but Units defaults to VOLTS.
Attach your device to the pair of BASC20 pins for the chosen channel so
that the more positive connection is to pin A and the more negative to pin C.
Figure 24 Analog Output Configuration
Vue de la page 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 52 53

Commentaires sur ces manuels

Pas de commentaire