2.7 Power Requirements
Limits
24 VAC/VDC ± 10%, 4763 Hz, 6 VA
2.8 General Specifications
Description
All inputs and outputs (except for relay outputs and communications ports)
are over-voltage protected up to 24 VAC and short-circuit protected.
Operating temperature to +60°C. Storage temperature 40°C to +85°C.
Relative humidity 1095%, non-condensing.
0.6 lbs. (0.27 kg).
2.9 LED Indicators
LED Indicator
Indication
UI1UI8 Configured as Analog Input
Green: > 1% of range, otherwise off
UI1UI8 Configured as Temperature Input
Green: sensor detected
UI1UI8 Configured as Contact Input
Green: contact closed, otherwise off
UI1UI8 Configured as Pulse Input
Green: pulse sensed, otherwise off
BI1BI4 Contact Closure
Green: contact closed, otherwise off
AO1AO4 Analog Output
Green: commanded output
BO1-BO4 Binary Output
Green: commanded output
Ethernet
Green: Link established; flashes with activity
2.10 Electromagnetic Compatibility
Standard
Test Method
Description
Test Levels
EN 55024
EN 61000-4-2
Electrostatic Discharge
6 kV contact
EN 55024
EN 61000-4-3
Radiated Immunity
10 V/m, 80 MHz to 1 GHz
EN 55024
EN 61000-4-4
Fast Transient Burst
1 kV clamp & 2 kV direct
EN 55024
EN 61000-4-5
Voltage Surge
1 kV L-L & 2 kV L-Earth
EN 55024
EN 61000-4-6
Conducted Immunity
10 V (rms)
EN 55024
EN 61000-4-11
Voltage Dips & Interruptions
1 Line cycle, 15 s @100% dip
EN 55022
CISPR 22
Radiated Emissions
Class A
EN 55022
CISPR 22
Conducted Emissions
Class B
CFR 47, Part 15
ANSI C63.4
Radiated Emissions
Class A